MIR IS LCPD Large Combustion Plants Automated Measuring System

MIR IS LCPD Large Combustion Plants Automated Measuring System 

100% compliant with European Directive 2001/80/EC MCERT (UK) approval (low & high ranges) and  NF (France) approval (with special accreditation for Large Power Plants applications) QAL 1 certified according to EN 14181 No system integration required (full turnkey system).

Аpplications:

  • Fuel-fired power plants
  • Coal-fired power plants
  • Biomass-fired power plants
  • Gas turbines (simple cycle and combined cycled)
  • Cogeneration

Features:

  • New sample probe
  • Simultaneous monitoring of 6 gases
  • Single-stream or multi-stream (multiplexing up to 4 streams)
  • No loss of solubles gases (NO2, SO2...) during sampling thanks to the use of patented permeation technique
  • Measurement principle: 

- Infrared Gas Filter Correlation (IR GFC) for NOx, SO2, CO & CO - Paramagnetic sensor for O2 (maintenance free)

  • Long multi-pass optical bench (12 meters) for unmatched accuracy
  • Direct measurement on dry basis (no need of H2O monitoring, no intereferences due to H2O)
  • Span gas injection on the probe using Cartified Reference Material as required in EN 14181 standard (QAL 3)

Specifications:

  • Packaged system for measurement of:NOx, CO, CO2, SO2, O2
  • Not suitable for double wall stacks/ducts
  • Sampling probe max. length: 1.5 meter
  • Flue gas max temperature: 400°C
  • Max operating temperature (analyzer): -15 to +50°C
  • Repeatability: <2% of the full scale (F.S)
  • Zero drift: <2% F.S / 30 days
  • Span drift: < 1% F.S / 7 days
  • Linearity: < 1% F.S
  • Power supply : 230V, 50-60 Hz

Certifications:

  • United Kingdom : MCERTS certification n°MC MC 040030/03 delivered by Sira
  • France : NF 379-02/01/06-03 certification delivered by ACIME